BN60 Circuit Breaker has 1 pole, 2 pole, 3 stage and 4 pole intended for use in circuit breakers,Used in shopping malls, base stations,home power into the line board control terminal.
Rated Current In: 6A,10A,16A,20A,25A,32A,40A,50A,63A
Breaking Capacity: 10KA
Trip curve:B、C、D
Product Implementation Standard:IEC60898.1,GB/T 10963.1
a)Ambient air temperature
Considering that high ambient temperature accelerates the aging of plastic parts, the
upper limit shall not exceed +40℃
Considering the excessively low ambient temperature changes the fit of structural
parts, the lower limit value is generally not less than -5℃. Considering the service
life of the circuit breaker, the average value of 24 hours is not more than +35℃.
Note: ① The working conditions with the lower limit of -10℃ or -25℃ shall be
declared to the company when ordering.
② If the upper limit exceeds +40℃ or the lower limit is lower than -25℃, the user
shall negotiate with the company.
b)Installation location
The altitude is not more than 2000m;
Protection circuit requirements;
Short-circuit current Ik calculated at installation point is not more than 6000A;
c)Atmospheric conditions:
The atmospheric relative humidity does not exceed 50% when the ambient air temperature is +40℃, and can have a higher relative humidity at lower temperatures. The monthly average maximum relative humidity in the wettest month is 90%, while the average minimum temperature in the month is +25℃ and the condensation on the product surface due to temperature changes.
d) Pollution level: Pollution level is III.
e) Installation category:
The installation category of Circuit Breaker protection circuit is Ⅲ
f)The traverse section is configured according to the maximum agreed heating current Ith of the circuit breaker.
Technical parameters of circuit breaker Chart 1,Chart 2
Chart 1 Overload protection feature parameter
1.13In |
1.45In |
No-trip within 1 hour |
No-trip within 1 hour |
Chart 2 Instantaneous protection trip interval
Trip curve type |
B |
C |
D |
Protected non-trip interval |
3In |
5In |
10In |
Protection trip interval |
5In |
10In |
15In |