Considering that high ambient temperature accelerates the aging of plastic parts, the
Considering the excessively low ambient temperature changes the fit of structural
parts, the lower limit value is generally not less than -5℃. Considering the service
life of the circuit breaker, the average value of 24 hours is not more than +35℃.
b)
Note: ① The working conditions with the lower limit of -10℃ or -25℃ shall be
declared to the company when ordering.
② If the upper limit exceeds +40℃ or the lower limit is lower than -25℃, the user
shall negotiate with the company.
Installation location
c)
The altitude is not more than 2000m;
Protection circuit requirements;
Short-circuit current Ik calculated at installation point is not more than 6000A;
Atmospheric conditions:
The atmospheric relative humidity does not exceed 50% when the ambient air
temperature is +40℃, and can have a higher relative humidity at lower temperatures.
The monthly average maximum relative humidity in the wettest month is 90%, while
the average minimum temperature in the month is +25℃ and the condensation on the
product surface due to temperature changes.
The installation category of Circuit Breaker protection circuit is Ⅲ
d) Pollution level: Pollution level is III.
e) Installation category:
.
f)The traverse section is configured according to the maximum agreed heating
current Ith of the circuit breaker